| Input |
| AC Input Voltage: |
90 to 320VAC |
| AC Input Frequency: |
45 to 66Hz |
| Surge protection: |
ANSI/IEEE Std. C62.41 to Category A, B, or C requirements, using a “Ring Wave” or
“Combination” waveform, at a level of 6kV |
| Output |
| Operational Output Power: |
150W continuous
170W, 10sec max. |
| Output Voltage: |
48 to 58VDC w/AC power, 42 to 58VDC with battery |
| Output Current: |
3.1A typical (crowbar limited beyond 5A DC) |
| Output Power Loading: |
Following GR-909 telephone lines in various states, e.g., ringing, off-hook, on-hook,
data, and video operation requirements. |
| Ripple: |
Less than 3mVrms |
| Noise: |
Less than 100mVp-p |
| Output Connection: |
Two terminal blocks accepting 16AWG, parallel connections |
| Local Alarms |
| System LED: |
Green Steady = System Output Normal, DC Output
Off = No AC or Battery Power |
| Battery LED: |
Yellow Steady = System on Battery
Off = Normal Mode |
| Replace Battery: |
Red Steady = Replace One or Two Battery Strings
Off = Batteries Within Parameters |
| Replace Battery A&B (Internal): |
Steady Red = Replace One or Both Battery Strings
Off = Batteries Within Parameters |
| Remote Alarms |
| Connection: |
Two five position IDC 24AWG, parallel connections |
| Pin 1 Alarm Return: |
Open collector return reference |
| Pin 2 AC Fail: |
On battery |
| Pin 3 Replace Battery: |
One or both battery strings failed periodic self test |
| Pin 4 Missing Battery: |
Less than eight batteries |
| Pin 5 Battery Low: |
Battery string voltage is less than 46.8VDC |
| Local - Audible Indicator |
| Alarm On: |
“Alarm Enable/Disable” toggle switch located on UPS
Batteries Below Voltage Parameters |
| Physical |
| FMPS |
|
| Dimensions |
|
| (in): |
14W x 23.75H x 5.5D |
| (mm): |
35.6W x 60.3H x 14D |
| Weight (lb/kg): |
25/11.3 |
| FMPS + Shipping Carton |
|
| Dimensions |
|
| (in): |
17W x 28.5H x 11.75D |
| (mm): |
35.6W x 60.3H x 14D |
| Weight (lb/kg): |
30/13.6 |
| Battery |
| Battery Type: |
Four or eight 7.2Ah Valve Regulated Lead Acid (VRLA) (Batteries sold separately) |
| Environment |
Operating
(with heater option):
(without heater option): |
-40 to 46°C (-40 to 115°F) plus solar loading, 0 to 95%
-10 to 46°C (14 to 115°F) plus solar loading, 0 to 95% humidity, 0 to 10000ft
(0 to 3000m) elevation |
| Storage: |
-15 to 85°C (-5 to 185°F), 0 to 95% humidity, 0 to 50000ft (0 to 15000m) elevation |
| Compliance |
CSA/UL 60950, EN 60950, EN 55022 Class B, FCC Part 15 Class B, GR-63 Sect 4.2 Fire Resistance,
GR-1089 Sect 3 Emissions, Sect 4 Lightning and AC Power Fault, Sect 7 Electrical Safety |
| Warranty |
| 3 year repair or replace |