 | Our catalogues |  |  | |
|
|  |
|
|
|
 |
 |
TRI-Power X33 |
|
 |
|
|
Three Phase UPS 20–800kVA
|
|
|
The TRI-POWER X33 is a high performance 20-800kVA UPS system with redundant processor controlling and modern fibre optic data transfer. The integrated intelligent Energie Management provides optimised efficiency operation. The TRI-POWER X33 protects all loads and is up to 99% efficient. This UPS is specially designed for telecom, industry and fire protecting applications.
- Online, VFI-SS-111
- Static and maintenance bypass
- THDI up to 5%
- Efficiency up to 99%
- LCD panel with back lighting
- Interface card
- Up to 8 systems in parallel
|
|
 |
|
|
|
| Size in kVA at cos phi = 0,8 |
20 |
30 |
40 |
60 |
80 |
Rectifier |
|
| Nominal Input Voltage (V): |
400V three phase (380V, 415V on request), 50/60Hz selectable |
| Nominal Input Voltage (V): |
+15 /-15 |
+15 /-15 |
+15 /-15 |
+15 /-15 |
+15 /-15 |
| Tolerance of voltage (without battery charge) (%): |
-25 |
-25 |
-25 |
-25 |
-25 |
| Frequency range (Hz): |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
| THD at input, incl. Filter + 12pulse rectifier (Option) (%): |
≤5 |
≤5 |
≤5 |
≤5 |
≤5 |
| Medium power factor, including THD-filter (cos phi): |
≥0,96 |
≥0,96
|
≥0,96 |
≥0,96 |
≥0,96 |
| Softstart adjustable (in sec.): |
0,10,20,30 |
| Battery charging current min. (A): |
2 |
2 |
2 |
5 |
5 |
| Battery charging current max. (A): |
46 |
64 |
91 |
126 |
171 |
Battery |
|
|
|
|
|
| Recommended power of battery needed, total (kW): |
16.9 |
25.3 |
33.6
|
50.4 |
67.2 |
| Power of battery in watt per each cell (W) (1 line): |
85.6 |
127.9 |
169.9 |
254.4 |
339.2 |
| Recommended nos. of Pb cells: |
198.0 |
198.0 |
198.0 |
198.0 |
198.0 |
| End of discharge voltage (V): |
316.8 |
316.8 |
316.8 |
384.0 |
384.0 |
Inverter |
|
|
|
|
|
| Nominal power at P. F. 0,8 inductive: |
20 |
30 |
40 |
60 |
80 |
| Nominal power at P. F. 1,0 (kW): |
16 |
24 |
32 |
48 |
64 |
| Nominal output current at 400VAC and 0,8 P. F. (A): |
29 |
44
|
58 |
87 |
116 |
| Nominal voltage (V): |
400V three phase (380V, 415V on request) + Neutral 50/60Hz |
| Crest factor at 100% balanced load: |
5 |
5 |
5 |
5 |
5 |
| Inverter efficiency at full nominal load (%): |
94.4% |
94.8% |
95.1% |
95.3% |
95.3% |
| Overload at 400VAC, 0.8 P. F. 150% Pn x 20 (min): |
20 |
20 |
20 |
20 |
20 |
| Overload at 400VAC, 0.8 P. F. 125% Pn x 90 (sec.): |
90 |
90 |
90 |
90 |
90 |
| 3 ph. Short circuit current 5 sec. (%) |
180 |
180 |
180 |
180 |
180 |
| 1 ph. Short circuit current 5 sec. (%) |
220 |
220 |
220 |
220
|
220 |
Reserve line (static switch): |
|
| Nominal input voltage (V): |
400V three phase (380V, 415V on request) + Neutral 50/60Hz |
| Nominal frequency (Hz): |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
Internal manual bypass (service bypass): |
Standard integrated |
General System Data |
|
| Radio interference suppression and immunity, acc. To: |
EN 50091-2
|
| Operating mode: |
Online, double conversion, acc. to VFI-SS-111 class A |
Efficiency, high efficiency plus mode (%): |
99.2 |
99.2 |
99.2 |
99.3 |
99.3 |
| Efficiency, high efficiency quality mode (%): |
97.1 |
97.1 |
97.1 |
97.1 |
97.3 |
| Efficiency, acc. to VFI-SS-111 (opt. load) (%): |
92.2 |
92.4 |
92.1 |
92.2 |
92.9 |
Norms, acc. to:
|
EN 50091 - 1 - 2 - 3 ; IEC 62040 - 1 - 2 - 3; VDE 0558, VFI-SS-111 Klasse A |
| MTBF (mean time between failure): |
20.000Hrs |
| Parallel mode, n+1 systems, up to: |
8 |
8 |
8 |
8 |
8 |
| Cabinet type: |
Industry steel cabinet, RAL 7035 |
| Cooling: |
Self cooling, redundancy fans |
Dimensions + Weights (standard) |
|
|
|
|
|
| Height (mm): |
1200 |
1200 |
1200 |
1400 |
1400 |
| Width (mm): |
555 |
555 |
555 |
800 |
800 |
| Depth (mm): |
720 |
720 |
720 |
740 |
740 |
| Weight UPS (kg): |
230 |
282 |
330 |
450 |
550 |
| Footprint (m2): |
0.47 |
0.47 |
0.47 |
0.47 |
0.60 |
| Load capacity (kg/m2): |
535 |
588 |
642 |
791 |
914 |
Interfaces |
|
| |
1. Serial RS 232, Sub-D 9pin, standard protocol, Male
2. Serial RS 232, Sub-D 9pin, J-BUS, Male
3. Serial RS 232, Sub-D 9pin, MOD-BUS, Male
4. Serial RS 232, Sub-D 9pin, PROFIBUS-Connector, Male
5. IBM AS400, Sub-D 9pin, Female
6. Potential free Relays, 10 + 5 Indications, programmable
7. GenSet operation, stop battery charging, input
8. GenSet operation, synchronising free running
9. EPO emergency power off, potential free input
9. EPO emergency power off, potential free output
11. Fibre optic for remote control (potential free) TX
12. Fibre optic up to 8-systems parallel (pot. free) RX/TX
13. SNMP-connector RS232, Sub-D 9pin for SNMP-Module |
| Size in kVA at cos phi = 0,8 |
100 |
120 |
160 |
200 |
250 |
300 |
400 |
600 |
Rectifier
Nominal Input Voltage (V): |
400V three phase (380V, 415V on request), 50/60Hz selectable |
| Nominal Input Voltage (V): |
+15 /-15 |
+15 /-15 |
+15 /-15 |
+15 /-15 |
+15 /-15 |
+15 /-15 |
+15 /-15 |
+15 /-15 |
| Tolerance of voltage (without battery charge) (%): |
-25 |
-25 |
-25 |
-25 |
-25 |
-25 |
-25 |
-25 |
| Frequency range (Hz): |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
| THD at input, incl. Filter + 12pulse rectifier (Option) (%): |
≤5 |
≤5 |
≤5 |
≤5 |
≤5 |
≤5 |
≤5 |
≤5 |
| Medium power factor, including THD-filter (cos phi): |
≥0,96 |
≥0,96
|
≥0,96 |
≥0,96 |
≥0,96 |
≥0,96 |
≥0,96 |
≥0,96 |
| Softstart adjustable (in sec.): |
0,10,20,30 |
| Battery charging current min. (A): |
5 |
5 |
5 |
5 |
10 |
10 |
10 |
30 |
| Battery charging current max. (A): |
216 |
252 |
342 |
414 |
522 |
536 |
860 |
1055 |
Battery
Recommended power of battery needed, total (kW): |
83.9 |
100.7 |
134.3
|
167.9 |
210.5 |
252.1 |
333.3 |
495.9 |
| Power of battery in watt per each cell (W) (1 line): |
424.0 |
508.8 |
678.3 |
847.9 |
1063.3 |
1050.4 |
1388.9 |
2066.1 |
| Recommended nos. of Pb cells: |
198.0 |
198.0 |
198.0 |
198.0 |
198.0 |
240.0 |
240.0 |
240.0
|
| End of discharge voltage (V): |
316.8 |
316.8 |
316.8 |
384.0 |
384.0 |
384.0 |
384.0 |
384.0 |
Inverter
Nominal power at P. F. 0,8 inductive: |
100 |
120 |
160 |
200 |
250 |
300 |
400 |
600 |
| Nominal power at P. F. 1,0 (kW): |
80 |
96 |
128 |
160 |
200 |
240 |
320 |
480 |
| Nominal output current at 400VAC and 0,8 P. F. (A): |
145 |
174
|
231 |
289 |
361 |
434 |
578 |
867 |
| Nominal voltage (V): |
400V three phase (380V, 415V on request) + Neutral 50/60Hz |
| Crest factor at 100% balanced load: |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
| Inverter efficiency at full nominal load (%): |
95.3% |
95.3% |
95.3% |
95.3% |
95.0% |
95.2% |
96.0% |
96.8% |
| Overload at 400VAC, 0.8 P. F. 150% Pn x 20 (min): |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
| Overload at 400VAC, 0.8 P. F. 125% Pn x 90 (sec.): |
90 |
90 |
90 |
90 |
90 |
90 |
90 |
90 |
| 3 ph. Short circuit current 5 sec. (%) |
180 |
180 |
180 |
180 |
180 |
180 |
180 |
180 |
| 1 ph. Short circuit current 5 sec. (%) |
220 |
220 |
220 |
220
|
220 |
220 |
220 |
220 |
Reserve line (static switch):
Nominal input voltage (V): |
400V three phase (380V, 415V on request) + Neutral 50/60Hz |
| Nominal frequency (Hz): |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
45–65 |
Internal manual bypass (service bypass): |
Standard integrated |
General System Data
Radio interference suppression and immunity, acc. To: |
EN 50091-2
|
| Operating mode: |
Online, double conversion, acc. to VFI-SS-111 class A |
Efficiency, high efficiency plus mode (%): |
99.3 |
99.3 |
99.3 |
99.3 |
99.2 |
99.2 |
99.2 |
99.3 |
| Efficiency, high efficiency quality mode (%): |
97.3 |
97.3 |
97.5 |
97.5 |
97.5 |
97.5 |
97.5 |
97.5 |
| Efficiency, acc. to VFI-SS-111 (opt. load) (%): |
93.8 |
93.6 |
94.4 |
94.7 |
93.8 |
94.03 |
94.5 |
94.9 |
Norms, acc. to:
|
EN 50091 - 1 - 2 - 3 ; IEC 62040 - 1 - 2 - 3; VDE 0558, VFI-SS-111 Klasse A |
| MTBF (mean time between failure): |
20.000Hrs |
| Parallel mode, n+1 systems, up to: |
8 |
8 |
8 |
8 |
8 |
8 |
8 |
8 |
| Cabinet type: |
Industry steel cabinet, RAL 7035 |
| Cooling: |
Self cooling, redundancy fans |
Dimensions + Weights (standard)
Height (mm): |
1900 |
1900 |
1900 |
1900 |
1950 |
1900
|
1900 |
1900 |
| Width (mm): |
800 |
800 |
800 |
800 |
1100 |
1630 |
1630 |
3200 |
| Depth (mm): |
800 |
800 |
800 |
800 |
800 |
800 |
1000 |
1000 |
| Weight UPS (kg): |
640 |
650 |
770 |
810 |
1650 |
2200 |
2600 |
4000 |
| Footprint (m2): |
0.88 |
0.88 |
0.88 |
1.50 |
2.70 |
2.70 |
2.70 |
2.70 |
| Load capacity (kg/m2): |
1045 |
1591 |
1875 |
1200 |
1074 |
1148 |
1444 |
1778 |
Interfaces |
|
| |
1. Serial RS 232, Sub-D 9pin, standard protocol, Male
2. Serial RS 232, Sub-D 9pin, J-BUS, Male
3. Serial RS 232, Sub-D 9pin, MOD-BUS, Male
4. Serial RS 232, Sub-D 9pin, PROFIBUS-Connector, Male
5. IBM AS400, Sub-D 9pin, Female
6. Potential free Relays, 10 + 5 Indications, programmable
7. GenSet operation, stop battery charging, input
8. GenSet operation, synchronising free running
9. EPO emergency power off, potential free input
9. EPO emergency power off, potential free output
11. Fibre optic for remote control (potential free) TX
12. Fibre optic up to 8-systems parallel (pot. free) RX/TX
13. SNMP-connector RS232, Sub-D 9pin for SNMP-Module |
|
|
|
|
|