| Model |
IGBT 10 |
IGBT 15 |
IGBT 20 |
IGBT 30 |
IGBT 45 |
| Power (kVA) |
10 |
15 |
20 |
30 |
45 |
| INPUT |
| Power Factor |
> 0,98 |
| Voltage |
230/400 VAC 3phasen +N, ± 20% |
| By-pass Voltage |
230/400 VAC 3phasen +N, ± 20% |
| Input THDI |
< 4% |
| Input frequenzy |
50Hz / 60 Hz ± 5% |
| EMI |
EN50091-2 Class A |
| OUTPUT |
| Power (kW) |
8 |
12 |
16 |
24 |
36 |
| Power Factor |
0.8 |
| Voltage |
230/400 VAC 3phase +N, ± 1% |
| Frequency |
50 Hz / 60Hz |
| Frequency tolerance |
± 2% (line synchronized); ± 0.2% (free running) |
| Efficiency |
up to95% |
| Crest Faktor |
3 : 1 |
| Overload protection |
(100%-125% load: 10min) (125%-150% load: 1min) (>150% load: by pass) |
| Short circuit protection |
Electronic short circuit protection |
| THD (at 100% linear load) |
< 3% |
| BATTERIES |
| Typ |
Sealed Lead Acid - Maintenance Free |
| Number of Batteries |
2x30 batteries |
| End of discharge voltage |
2x300 VDC |
| Ambient temperature °C |
25 °C |
| Battery protection |
Wall mounted circuit breaker and fuse |
| Typical recharge time |
6 hours |
| Battery test |
Automatic or manual |
| GENERAL |
| Human interface |
Text LCD panel, mimic diagram LED panel |
| Communication |
RS232 and Dry contacts |
| Software |
T-Mon UPS Management Software (3 clients standard) |
| Overtemperature proctection |
Electronic overtemperature protection |
| Temperature range |
0°C - 40°C |
| Protection degree |
IP 20 |
| Humidty |
90% non condensing
|
| Altitude |
< 1000m above sea level |
| Accoustic noise |
< 50 dBA |
| Weight w/o batteries (kg) |
96 |
105 |
110 |
183 |
196 |
| Dimensions HxBxD (mm) |
1030x375x725 |
1145x495x835 |
| OPTIONS |
| Transformer |
Galvanic isolation transformer at the input & output |
| Parallel operation |
1+3 Systeme (N+1 redundant, symetruc parallell) |
| |
|
| |
|
| Model |
IGBT 60 |
IGBT 80 |
IGBT 100 |
IGBT 120 |
IGBT 160 |
| Power (kVA) |
60 |
80 |
100 |
120 |
160 |
| INPUT |
| Power Factor |
> 0,98 |
| Voltage |
230/400 VAC 3phasig +N, ± 20% |
| By-pass Voltage |
230/400 VAC 3phasig +N, ± 20% |
| Input THDI |
< 4% |
| Input frequency |
50Hz / 60 Hz ± 5% |
| EMI |
EN50091-2 Classe A |
| OUTPUT |
| Power (kW) |
48 |
64 |
80 |
96 |
128 |
| Power factor |
0.8 |
| Voltage |
230/400 VAC 3phase +N, ± 1% |
| Frequency |
50 Hz / 60Hz |
| Frequency tolerance |
± 2% (line synchronized); ± 0.2% (free running) |
| Efficiency |
up to 95% |
| Crest factor |
3 : 1 |
| Overload protection |
(100%-125% load: 10min) (125%-150% load: 1min) (>150% load: by pass) |
| Short circuit protection |
Electronic short circuit protection |
| THD (at 100% linear load) |
< 3% |
| BATTERIES |
| Typ |
Sealed Lead Acid - Maintenance Free |
| Number of batteris |
2x30 batteries |
| End of discharge voltage |
2x300 VDC |
| Ambient temperature °C |
25 °C |
| Battery protection |
Wall mounted circuit breaker and fuse |
| Typical recharge time |
6 hours |
| Battery test |
Automatic or manual |
| GENERAL |
| Human interface |
Text LCD panel, mimic diagram LED panel |
| Communication |
RS232 and Dry contacts |
| Software |
T-Mon UPS Management Software (3 clients standard) |
| Overtemperature protection |
Electronic overtemperature protection |
| Temperature range |
0°C - 40°C |
| Protection degree |
IP 20 |
| Humidity |
90% non condensing |
| Altitude |
< 1000m above sea level |
| Accoustic noise |
< 50 dBA |
| Weight w/o (kg) |
225 |
350 |
350 |
375 |
425 |
| Dimensions HxBxD (mm): |
1445x495x835
|
1900x780x890 |
1900x780x890 |
| OPTIONS |
| Transformator |
Galvanic isolation transformer at the input & output |
| Parallel operation |
1+3 Systems (N+1 redundant, redundant, symetric parallel) |
| |
|
| |
|
| Model |
IGBT 200 |
| Power (kVA) |
200 |
|
| INPUT |
| Power Factor |
> 0,98 |
| Voltage |
230/400 VAC 3phasig +N, ± 20% |
| By-passVoltage |
230/400 VAC 3phasig +N, ± 20% |
| Input THDI |
< 4% |
| Input frequency |
50Hz / 60 Hz ± 5% |
| EMI |
EN50091-2 Klasse A |
| OUTPUT |
| Power (kW) |
160 |
| Power Factor |
0.8 |
| Voltage |
230/400 VAC 3phase +N, ± 1% |
| Frequency |
50 Hz / 60Hz |
| Frequency tolerance |
± 2% (line synchronized); ± 0.2% (free running) |
| Efficiency |
up to 95% |
| Crest factor |
3 : 1 |
| Overload protection |
(100%-125% load: 10min) (125%-150% load: 1min) (>150% load: By-pass) |
| Short circuit protection |
Electronic short circuit protection |
| THD (at 100% linear load) |
< 3% |
| BATTERIES |
| Typ |
wartungSealed Lead Acid - Maintenance Free |
| Number of batteries |
2x30 batteries |
| End of discharge |
2x300 VDC |
| Ambient temperature °C |
25 °C |
| Battery protection |
Wall mounted circuit breaker and fuse |
| Typical recharge time |
6 hours |
| Battery test |
Automatic or manual |
| GENERAL |
| Human interface |
Text LCD panel, mimic diagram LED panel |
| Communication |
RS232 and Dry contacts |
| Software |
T-Mon UPS Management Software (3 clients standard) |
| Overtemperature proctection |
Electronic overtemperature protection |
| Temperature range |
0°C - 40°C |
| Protection degree |
IP 20 |
| Humidity |
90% nicht kondensierend |
| Altitude |
< 1000m über NN |
| Accoustic noise |
< 50 dBA |
| Weight w/o (kg) |
495 |
| Dimensions HxBxD (mm): |
1900x780x890 |
| OPTIONS |
| Transformator |
Galvanic isolation transformer at the input & output |
| Parallel operation |
1+3 Systems (N+1 redundant, redundant, symetric parallel) |