Total Power Solutions
Our catalogues

Our catalogues

German    English    French
TRI-Power X33 IGBT

TRI-Power X33 IGBT

3phase UPS 10 to 200kVA

TRI-Power X33 IGBT
Data up to 45kVA
Data up to 120kVA
Data up to 200kVA
Downloads
Source of supply

The IGBT rectifier technology ensures a reduction of consumption of reactive power to minimum levels. This results in lower electricity bills and smaller genset sizes. Small footprint and light weight makes installations easier and less space is necessary. Compared to 6 or 12 pulse rectifier systems the heat dissipation is lower and the air condition size can be dimensioned smaller. This results in less CO2 production saving money and protecting our environment. The Tri Power X33 IGBT UPS can be used for any kind of load i.e. IT, Industry and Telecom.

  • Model range available: 10 to 200kVA
  • IGBT Rectifier
  • Low Input THD <4%
  • RS232 and dry contacts
  • VFI-SS-111 according to IEC 62040-3
  • High efficiency up to 95%

Variants Technical data

 

Technical Data
Model IGBT 10 IGBT 15 IGBT 20 IGBT 30 IGBT 45
Power (kVA) 10 15 20 30 45
INPUT
Power Factor > 0,98
Voltage 230/400 VAC 3phasen +N, ± 20%
By-pass Voltage 230/400 VAC 3phasen +N, ± 20%
Input THDI < 4%
Input frequenzy 50Hz / 60 Hz ± 5%
EMI EN50091-2 Class A
OUTPUT
Power (kW)  8 12 16 24 36
Power Factor 0.8
Voltage 230/400 VAC 3phase +N, ± 1%
Frequency 50 Hz / 60Hz
Frequency tolerance ± 2% (line synchronized); ± 0.2% (free running)
Efficiency up to95%
Crest Faktor 3 : 1
Overload protection (100%-125% load: 10min) (125%-150% load: 1min) (>150% load: by pass)
Short circuit protection Electronic short circuit protection
THD (at 100% linear load) < 3%
BATTERIES
Typ  Sealed Lead Acid - Maintenance Free
Number of Batteries 2x30 batteries
End of discharge voltage 2x300 VDC 
Ambient temperature °C 25 °C
Battery protection Wall mounted circuit breaker and fuse
Typical recharge time 6 hours
Battery test Automatic or manual
GENERAL
Human interface Text LCD panel, mimic diagram LED panel
Communication RS232 and Dry contacts
Software T-Mon UPS Management Software (3 clients standard)
Overtemperature proctection Electronic overtemperature protection
Temperature range 0°C - 40°C
Protection degree  IP 20
Humidty

 90% non condensing

Altitude < 1000m above sea level
Accoustic noise < 50 dBA
Weight w/o batteries (kg) 96 105 110 183 196
Dimensions HxBxD (mm) 1030x375x725 1145x495x835
OPTIONS
Transformer Galvanic isolation transformer at the input & output
Parallel operation  1+3 Systeme (N+1 redundant, symetruc parallell)
   
   
Model IGBT 60  IGBT 80  IGBT 100  IGBT 120  IGBT 160
Power (kVA) 60  80  100  120  160
INPUT
Power Factor > 0,98
Voltage 230/400 VAC 3phasig +N, ± 20%
By-pass Voltage 230/400 VAC 3phasig +N, ± 20%
Input THDI < 4%
Input frequency 50Hz / 60 Hz ± 5%
EMI EN50091-2 Classe A
OUTPUT
Power (kW) 48  64  80  96  128
Power factor 0.8
Voltage 230/400 VAC 3phase +N, ± 1%
Frequency 50 Hz / 60Hz
Frequency tolerance ± 2% (line synchronized); ± 0.2% (free running)
Efficiency up to 95%
Crest factor 3 : 1
Overload protection (100%-125% load: 10min) (125%-150% load: 1min) (>150% load: by pass)
Short circuit protection Electronic short circuit protection
THD (at 100% linear load)  < 3%
BATTERIES
Typ Sealed Lead Acid - Maintenance Free
Number of batteris 2x30 batteries
End of discharge voltage 2x300 VDC
Ambient temperature °C 25 °C
Battery protection Wall mounted circuit breaker and fuse
Typical recharge time 6 hours
Battery test Automatic or manual
GENERAL
Human interface Text LCD panel, mimic diagram LED panel
Communication RS232 and Dry contacts
Software T-Mon UPS Management Software (3 clients standard)
Overtemperature protection Electronic overtemperature protection
Temperature range 0°C - 40°C
Protection degree IP 20
Humidity 90% non condensing
Altitude < 1000m above sea level
Accoustic noise < 50 dBA
Weight w/o (kg)  225  350  350  375  425
Dimensions HxBxD (mm):

    1445x495x835

          1900x780x890  1900x780x890
 OPTIONS
Transformator Galvanic isolation transformer at the input & output
Parallel operation 1+3 Systems (N+1 redundant, redundant, symetric parallel)
   
   
Model IGBT 200   
Power (kVA)  200  
INPUT
Power Factor > 0,98
Voltage 230/400 VAC 3phasig +N, ± 20%
By-passVoltage 230/400 VAC 3phasig +N, ± 20%
Input THDI < 4%
Input frequency 50Hz / 60 Hz ± 5%
EMI EN50091-2 Klasse A
OUTPUT
Power (kW) 160
Power Factor 0.8
Voltage 230/400 VAC 3phase +N, ± 1%
Frequency 50 Hz / 60Hz
Frequency tolerance ± 2% (line synchronized); ± 0.2% (free running)
Efficiency up to 95%
Crest factor 3 : 1
Overload protection (100%-125% load: 10min) (125%-150% load: 1min) (>150% load: By-pass)
Short circuit protection Electronic short circuit protection
THD (at 100% linear load)  < 3%
BATTERIES
Typ wartungSealed Lead Acid - Maintenance Free
Number of batteries 2x30 batteries
End of discharge 2x300 VDC
Ambient temperature °C 25 °C
Battery protection Wall mounted circuit breaker and fuse
Typical recharge time 6 hours
Battery test Automatic or manual
GENERAL
Human interface Text LCD panel, mimic diagram LED panel
Communication RS232 and Dry contacts
Software T-Mon UPS Management Software (3 clients standard)
Overtemperature proctection Electronic overtemperature protection
Temperature range 0°C - 40°C
Protection degree IP 20
Humidity 90% nicht kondensierend
Altitude < 1000m über NN
Accoustic noise < 50 dBA
Weight w/o (kg) 495
Dimensions HxBxD (mm): 1900x780x890
 OPTIONS
Transformator Galvanic isolation transformer at the input & output
Parallel operation 1+3 Systems (N+1 redundant, redundant, symetric parallel)